• ATMS234.jpg

Aquablend 2000 Upgrade Cartridge with Thermal Flush (for Old Style Aquablend 2000 Superseded Model - Pre 2009)

The Aquablend 2000 Upgrade Cartridge provides the opportunity to upgrade existing pre-2009 Aquablend 2000 with a complete cartridge changeover, enhancing the technology and extending the life of the existing Aquablend TMV.

Key features

  • Only the cartridge is swapped over - no need to replace TMV body
  • Thermal flush activation incorporated within the headworks for superior flush capabilities
  • Save on yearly servicing costs
  • Save time on servicing
  • Products

    Order code Aquablend 2000 Upgrade Cartridge with Thermal Flush (for Old Style Aquablend 2000 Superseded Model - Pre 2009)
    ATMS234
    Upgrade Cartridge with ThermalFlush (for Old Style Aquablend 2000 - Pre 2009)
  • Temperature Adjustment Range 38 to 50C
    Dynamic Inlet Pressures 20kPa Min - 500kPa Max
    Static Inlet Pressure 1600kPa Max
    Flow Rates 38lpm@300kPa pressure loss
    Minimum Flow Rate for stable outlet temperature 4 litres/min
    Inlet size 1/2" MI comp (ATM711) or 3/4"FI (ATM713)
    Outlet size 3/4" BSP MI
    Inlet Temperatures Cold Supply: Min 5 C Max 30 C Hot Supply: Min 55 C Max 90 C
    For optimum operation it is recommended that the hot and cold water supply pressures be balanced within +/- 10%. Hot to Mix temperature differential required for stable operation is minimum 10C. * Enware products are to be installed in accordance with the Plumbing Code of Australia and AS/NZS3500. NOTE: Enware Australia advises: 1. Due to ongoing Research and Development, specifications may change without notice. 2. Component specifications may change on some export models.
  • Document type File type
    Installation guide pdf
Email Us