• ATM700.jpg

Aquablend 1500 Thermostatic Mixing Valve

Aquablend's technology provides superior control when scald protection is needed most even under changing pressure and temperature conditions, and also at ambient start up. The proven performance, reliability and low 'whole of life' cost makes Aquablend a popular choice with specifiers, engineers, plumbers and property owners. With the inclusion of the new thermal flush feature, maintaining a healthy water service has never been easier. Suitable for health and general applications. NSW Health approval for use in healthcare in NSW.

Key features

  • Australian design and manufacture and Standards Licensed to AS4032.1
  • Thermal flush activation incorporated within the headworks for superior flush capabilities
  • Scald and thermal shock protection with rapid thermal shut-off should either the cold or hot water supply failure
  • Highly responsive mixed temperature control (+/- 2 Degrees Celcius) under changing inlet temperature and pressure conditions
  • Delivers excellent flow, operating at a minimum pressure of 20kPa
  • Flexible installation - inlet and outlet connections may be rotated to suit pipework design
  • Products

    Order code Aquablend 1500 Thermostatic Mixing Valve
    ATM700
    15mm MI Inlet 20mm MI Outlet with 15mm Adaptor
    ATMS700-350
    Aquablend 1500 350 x 350 cabinet - HW/CW inlet at bottom
    ATMS700PRV-430
    Aquablend 1500 430 x 500 cabinet - HW/CW inlet at bottom - with 2 x PRV
    ATMS700PRVSF-430
    Aquablend 1500 430 x 500 cabinet - HW/CW inlet at bottom - with 2 x PRV - Smartflow enabled
    ATMS700SF-350
    Aquablend 1500 350 x 350 cabinet - HW/CW inlet at bottom - Smartflow enabled
    ATMS700VC-350
    Aquablend 1500 350 x 350 cabinet and TMV only
    ATMS700VCPRV-430
    Aquablend 1500 430 x 500 cabinet and TMV only - with 2 x PRV
    ATMS700VCPRVSF-430
    Aquablend 1500 430 x 500 cabinet and TMV only - with 2 x PRV - Smartflow enabled
    ATMS700VCSF-350
    Aquablend 1500 350 x 350 cabinet and TMC only - Smartflow enabled
    ATMS718-350
    Aquablend 1500 350 x 350 cabinet - CW bypass at bottom HW/CW inlet at top
    ATMS718RW-350
    Aquablend 1500 350 x 350 cabinet - CW bypass at bottom HW/CW inlet at top. Additional RW pipe in top/out bottom
    ATMS718RWSF-350
    Aquablend 1500 350 x 350 cabinet - CW bypass at bottom HW/CW inlet at top. Additional RW pipe in top/out bottom - Smartflow enabled
    ATMS718SF-350
    Aquablend 1500 350 x 350 cabinet - CW bypass at bottom HW/CW inlet at top - Smartflow enabled
    ATMS719-350
    Aquablend 1500 350 x 350 cabinet - CW bypass at bottom HW/CW inlet at bottom
    ATMS719PRV-430
    Aquablend 1500 430 x 500 cabinet - CW bypass at bottom HW/CW inlet at bottom - with 2 x PRV
    ATMS719PRVRW-430
    Aquablend 1500 430 x 500 cabinet - CW bypass at bottom HW/CW inlet at bottom. Additional RW pipe in top/out bottom - with 2 x PRV
    ATMS719PRVRWSF-430
    Aquablend 1500 430 x 500 cabinet - CW bypass at bottom HW/CW inlet at bottom. Additional RW pipe in top/out bottom - with 2 x PRV - Smartflow enabled
    ATMS719PRVSF-430
    Aquablend 1500 430 x 500 cabinet - CW bypass at bottom HW/CW inlet at bottom - with 2 x PRV - Smartflow enabled
    ATMS719RW-350
    Aquablend 1500 350 x 350 cabinet - CW bypass at bottom HW/CW inlet at bottom. Additional RW pipe in top/out bottom
    ATMS719RWSF-350
    Aquablend 1500 350 x 350 cabinet - CW bypass at bottom HW/CW inlet at bottom. Additional RW pipe in top/out bottom - Smartflow enabled
    ATMS719SF-350
    ATMS750-350
    Aquablend 1500 350 x 350 cabinet - CW/HW bypass at bottom HW/CW inlet at bottom
    ATMS750PRV-430
    Aquablend 1500 430 x 500 cabinet - HW/CW bypass at bottom HW/CW inlet at bottom - with 2 x PRV
    ATMS750PRVSF-430
    Aquablend 1500 430 x 500 cabinet - HW/CW bypass at bottom HW/CW inlet at bottom - with 2 x PRV - Smartflow enabled
    ATMS750SF-350
    Aquablend 1500 350 x 350 cabinet - CW/HW bypass at bottom HW/CW inlet at bottom - Smartflow enabled
    ATMS751-350
    Aquablend 1500 350 x 350 cabinet - CW/HW bypass at bottom HW/CW inlet at top
    ATMS751SF-350
    Aquablend 1500 350 x 350 cabinet - CW/HW bpass at bottom HW/CW inlet at top - Smartflow enabled
    Supplied complete with isolating valves, non-returns and dual stage strainers incorporating temperature/pressure test ports.
  • Temperature Adjustment Range 35 to 48C
    Dynamic Inlet Pressures 20kPa Min - 500kPa Max
    Static Inlet Pressure 1600kPa Max
    Flow Rates 39lpm@300kPa pressure loss
    Minimum Flow Rate for stable outlet temperature 4 litres/min
    Inlet size 1/2" compression nuts
    Outlet size 1" complete with 1"x1/2" & 1"x 3/4" BSP adaptors
    Inlet Temperatures Cold Supply: Min 5 C Max 30 C Hot Supply: Min 55 C Max 90 C
    For optimum operation it is recommended that the hot and cold water supply pressures be balanced within +/- 10%. Hot to Mix temperature differential required for stable operation is minimum 10C. * Enware products are to be installed in accordance with the Plumbing Code of Australia and AS/NZS3500. NOTE: Enware Australia advises: 1. Due to ongoing Research and Development, specifications may change without notice. 2. Component specifications may change on some export models.
  • ATM700 Line Drawing
Email Us