Enware Aquablend thermostatic technology provides superior control to ensure scald protection and temperature control under the most challenging conditions of hydraulic pressure and temperature variation and at ambient start up. Lead Free brass and the updated Lift Lever thermal flush function for fast and simple thermal disinfection, helps to maintain healthy water systems. The proven performance, reliability and low whole of life cost makes Aquablend the popular choice with specifiers, engineers, plumbers and property owners. Also available in a range of pre-plumbed cabinets for simple installation and servicing or equipped with Smartflow Warm Water monitoring systems, the Aquablend 1500 is the ideal choice of thermostatic mixing valve for Hospital, Health care and commercial applications.
Key Selling Points
- Thermal Flush Lift Lever activation incorporated within the headworks for superior flush capabilities
- Scald and thermal shock protection with rapid thermal shut-off should either the cold or hot water supply fails
- Highly responsive temperature control, maintaining outlet temperature within +/- 2˚C under changing inlet temperature and pressure conditions
- Delivers high flow at low pressure loss
- Supplied complete with isolating valves, non-return valves and dual stage strainers incorporating temperature/ pressure test ports
- Flexible installation - can be upside down or sideways, inlet and outlet connections may be rotated to suit pipework design
- Available in a range of pre-plumbed configurations mounted in lockable stainless steel cabinets
- Standards licensed to AS4032.1 - Thermostatic Mixing Valves
- Certifications
- WMKA25301_AS4032.1_LF,Health Approved - NSW,Lead Free
- Minimum Cold Temperature Supply (Deg C)
- 5
- Maximum Cold Temperature Supply (Deg C)
- 30
- Minimum Hot Temperature Supply (Deg C)
- 55
- Maximum Hot Temperature Supply (Deg C)
- 90
- Minimum Thermostatic Temperature (Deg C)
- 35
- Maximum Thermostatic Temperature (Deg C)
- 48
- Maximum Flow Rate (L/min@200kPa pressure loss)
- 39
- Minimum Flow Rate for Stable Outlet Temperature (L/min)
- 4
- Minimum Flow Rate (L/min)
- 2
- Maximum Flow Rate (L/min)
- 45
- Inlet Connection
- 1/2" MI with compression nuts or 3/4" MI
- Outlet Connection
- 1" with 1"x1/2" and/or 1"x 3/4" BSP adaptors