Aquablend 1500 Thermostatic Mixing Valve Pre-Plumbed in Stainless Steel Wall Cabinet for recess or exposed positions. The proven performance, reliability and low ‘whole of life’ cost makes Aquablend a popular choice with specifiers, engineers, plumbers and property owners. With the inclusion of the thermal flush feature, maintaining a healthy water service has never been easier. Suitable for health and general applications. NSW Health approval for use in healthcare in NSW.

Key Selling Points

  • Lift Lever Thermal Flush activation incorporated within the headworks for faster, safer, more efficient thermal disinfection capability
  • Manufactured from Lead Free brass components - including pipe fittings
  • Scald and thermal shock protection with rapid thermal shut-off should either the cold or hot water supply fail
  • Highly responsive temperature control, maintaining outlet temperature within +/- 2?C under changing inlet temperature and pressure conditions
  • Delivers high flow at low pressure loss
  • Supplied complete with isolating valves, non-return valves and dual stage strainers incorporating temperature/ pressure test ports
  • Pipework is designed to reduce flow restrictions and minimise bacterial capture points to reduce the risk of bacterial contamination
  • Flexible installation - can be upside down or sideways, inlet and outlet connections may be rotated to suit pipework design
  • A range of suitable Stainless Steel lids are available for this model:
  • ATMSHL-350 - Hinged Lid with wall flange
  • ATMSXP-350 - Exposed Lid
  • ATMSSEC-350 - Secure/Heavy Duty Lid
  • Standards licensed to AS4032.1 - Thermostatic Mixing Valves
  • NSW Health Approved

Certifications
WMKA25301_AS4032.1_LF,Health Approved - NSW,Lead Free
Minimum Cold Temperature Supply (Deg C)
5
Maximum Cold Temperature Supply (Deg C)
30
Minimum Hot Temperature Supply (Deg C)
55
Maximum Hot Temperature Supply (Deg C)
90
Minimum Thermostatic Temperature (Deg C)
35
Maximum Thermostatic Temperature (Deg C)
48
Maximum Flow Rate (L/min@200kPa pressure loss)
39
Minimum Flow Rate for Stable Outlet Temperature (L/min)
4
Minimum Flow Rate (L/min)
2
Maximum Flow Rate (L/min)
45
Inlet Connection
20mm(Nom.) OD Copper tails